Home backup power: a review of my own setup

Grid, inverter and generator in one cascade. What turned up when I drew the diagram of the setup for the first time and walked through it asking about failures.

The backup power setup in my country house worked fine: when the grid goes down, the house switches to an inverter with a battery, and after that to a petrol generator. But there was neither a diagram nor wire labelling in the cabinet.

One day I sat down and reviewed this setup the same way I would review someone else's system at work: with priorities, failures and the question "what happens if".

A cascade of two transfer switches

The setup is built as a cascade of two automatic transfer switches:

GRID ─────────┐
              ├─ switch 1 ─┐
INVERTER ─────┘            ├─ switch 2 ── distribution board, whole house
GENERATOR ─────────────────┘

The priority is: grid, then inverter, then generator.

  1. the grid is up: both switches sit on the first input, the house is powered from the grid;
  2. the grid is down: the smart relay brings up the inverter on its own, without the cloud, and the first switch moves over to it;
  3. on a timer the load should move to the generator, if its autostart is allowed;
  4. if autostart is not allowed, the inverter runs until the battery is drained.

The battery charges only from the grid. It does not charge from the generator.

Where the setup fails

On paper the design looked neat, until I walked through it asking about failures.

In practice there is no automatic generator takeover. The transfer timer is turned up to the maximum, and the generator is not set to autostart. This was done deliberately, to save fuel. The consequence is unpleasant: in a long outage the battery drains to zero, and the house goes dark.

At that point autostart is no longer possible: the start circuit is powered from the same drained battery. The generator can only be started by hand, with its own starter.

Autonomy is short and depends heavily on the load. The backup carries the whole house, there is no load separation. The inverter holds up to 5.5 kW, but by the datasheet estimate the battery lasts 20-25 minutes at that load.

LoadDatasheet estimate
500 Wabout 4 hours
2 kWabout an hour
5.5 kW20-25 minutes

The autonomy numbers in this review come from the datasheet, and that is its weak spot. The real ones appeared later, when I installed a monitor that watches the grid, the inverter and the generator. They turned out better than the estimate: at 500 W the battery holds 5.3 hours. There is a separate article about that.

There is no fuse on the DC side. This is the main finding of the review. The cables between the battery and the inverter are thick, there are no questions about the cross-section, but there is no separate fuse between them. The only protection is the electronics of the battery itself.

Overload and short circuit

It is easy to reassure yourself here. There is overload protection, and in two stages: a relay with a power threshold and the inverter's own protection. But both sit on the section from the inverter to the house.

A short-circuit current on the cable between the battery and the inverter physically bypasses them. A lithium iron phosphate battery of this size delivers thousands of amps in a short circuit, and the battery electronics may not react in time.

A fuse on the battery positive does not duplicate anything: it covers the only section that has no protection at all.

What else turned up

  • traces of heating on the power terminal block of one of the switches. It needs to be retightened and inspected;
  • a failure of the smart relay means a failure of the whole inverter stage. The upside is that it brings up the inverter locally and does not depend on the internet;
  • the generator's starter battery drains over months of sitting idle. Then manual start will not work either;
  • there is no explicit interlock between the two switches, only a mechanical one inside each;
  • the cabinet has neither wire labelling nor a diagram on the door;
  • one marking on a breaker matched the model name of the inverter. I lost time before I understood that it is the catalogue number of the breaker itself.

Something good turned up too: protection against electric shock also works in autonomous mode. The residual current devices trip both on the inverter and on the generator, because the neutral is grounded in both modes.

You can walk through any system the same way, if someone else built it and it "just works". The question "what happens if" is better asked before the first long outage.